General Features

  • RC range unit coolers have been designed to be installed inside cold rooms.
  • Their shape, being extremely compact, allows the installation also in cold rooms having very small dimensions.
  • All models nave a fin spacing of 5.3 mm. a geometry of 25×22 and a 3/8″ tube.
  • The ED version is fitted with defrosting heaters and is suitable for being used at low temperature applications.
  • The fan motors operate in the suction mode and prevent the condensate forming on the fan.

 

[/vc_column_text]
[vc_column_text pb_margin_bottom=”no” pb_border_bottom=”no” width=”1/1″ el_position=”first last”]

Coil

The coil is made of aluminium fins (fin spacing 5.3 mm.) and 3/8″ copper tube. It is tested with nitrogen at a pressure of 25 bar.

[/vc_column_text] [vc_column_text pb_margin_bottom=”no” pb_border_bottom=”no” width=”1/1″ el_position=”first last”]

Fan motor

The fan motor model in use has the following features :
* Manufactured following EN 60 335-1 laws with internal thermal protection
* Fan diameter 250 mm. 28 inclination
* Power supply 230-240V / 1 / 50-60 Hz
* IP 44 protection rate
* Operating temperature from -40 C to + 40 C
* Electrics made in conformity with 73/23 CEE for low-tension motors

[/vc_column_text] [vc_column_text pb_margin_bottom=”no” pb_border_bottom=”no” width=”1/1″ el_position=”first last”]

Housing

The housing is made of aluminium. The manufacturing solution used give the housing strength and guarantees
the absence of vibrations during the functioning. Screws, washers and nuts are made of stainless steel.

 

lato_1

 

lato collegamento elettrico electrical connection side

 

lato_2

 

lato collegamento frigorifero pipe connection side

 